Interceptors - Oil / Petrol
Forecourt Interceptors
Forecourt interceptors are full-retention interceptors specified to retain on site the maximum spillage likely to occur on a petrol filling station. They are required for both safety and environmental reasons and will treat spillages occurring during vehicle refueling and road tanker delivery. The size of the interceptor is increased in order to retain the possible loss of the contents of one compartment of a road tanker, which may be up to 7600 liters.
Downloads
| Aswaclear® Forecourt Interceptors from Molloy Precast | ||||||
| Reference and unit nominal size | Nominal Flow (l/s) |
Area Covered (m2) |
Maximum Silt storage Capacity (L) |
Oil retention capacity |
Total System Volume (L) | PDF Drawing Download |
| FC-NS-6-CH Buderus | 10 | 333 | 800 | 7600 | 10500 | |
| FC-NS-10-CC Buderus | 10 | 555 | 1000 | 7600 | 16000 | |
| FC-NS-20-HCC Buderus | 20 | 1110 | 2000 | 7600 | 16000 | Please contact us for this PDF drawing. |
| At 65mm rain per hour | Area for nominal flow |
Clean at 80% | Clean at 10-20% | |||
Reference Log:
FC =Fore Court;
NS = Nominal Size
10 = flow are in L/sec
C/H = Molloy Precast Tank type
Buderus = stainless steel coalescence fittings with automatic shut off valve
hdp = high density polypropylene coalescence filter with no valve